1
Power circuit
Three-phase supply passes through a 3-phase MCB and MCCB to the main contactor (MC MAIN). Star (MC STAR) and delta (MC DELTA) contactors reconfigure the motor windings. A thermal overload relay sits in series with the motor, and an ammeter with a selector switch monitors the R, S and T phase currents.
2
Control circuit
A Schneider TM221C16R PLC, powered from a 24 V DC supply, reads the Start, Stop and Emergency Stop inputs and drives four contactor coils. Timer T1 sets the star-to-delta changeover, timer T2 sets the braking duration, and interlocks prevent contactors from overlapping.
3
Braking circuit
When the braking contactor closes, AC is fed to a diode bridge rectifier. The resulting DC flows into two stator terminals, creating a static magnetic field that produces braking torque. After T2 expires the contactor opens so DC does not keep heating the winding.
4
Mechanical layout
The inside panel has three DIN-rail tiers: MCB and PLC, four contactors with the overload relay, and MCCB with the power supply. Terminal blocks sit at the bottom. The front door carries R/S/T indicator lamps, the ammeter, ON/OFF lamps, an emergency stop and PB ON / PB OFF buttons.